All references

Find the source for your panel.

Compare the document, panel series and conditions before comparing breaker names. This reference table records what the named documents print.

Quick answer

Eaton's catalog defines two kinds of breaker: "Specified breakers are listed by the manufacturer of the panelboard for use in a particular panel", and Classified breakers are "for use in place of the breakers specified on the panelboard" [E2 p.V1-T1-101]. UL ties a Classified breaker to the panelboards named on the compatibility list supplied with it [U1 items 97–99]. UL limits Classified breakers to systems of 120/240 V and 10 kA available short-circuit current or less [U1 item 97]. Eaton states its Classified breakers can be used "in applications up to and including 120/240 volts, 225 ampere (A) panels" [E4 p.2].

Three fictional breaker-like housings of different widths in front of blank document sheets.
AI-generated concept illustration. Appearance cannot establish compatibility. These fictional shapes do not represent any named family, pole count, rating or dimensional comparison. Not technical evidence.

How to use this chart

  1. Find the brand, the catalog number and the breaker types on your panel label. See How to read your panel label (diagram D1).
  2. Find your panel brand in the chart. Each row quotes or lists what the cited document prints, with its source ID and page.
  3. Open the cited document and page. If the chart and your label disagree, the label wins.
Document lookup steps (no verdicts)
  1. 01

    Record the label

    Keep the complete panel identifier, breaker-type list, date and ratings together. Q7

  2. 02

    Read the exact document

    Keep the maker, document revision and original page with the record. E1

  3. 03

    Retain conditions and conflicts

    Record the printed limits and the panel maker’s separate statement. Q1

  4. 04

    Bring the references to an electrician

    A document search does not decide what may be installed. S10

Original drawing and source annotations

The original drawing is schematic, not a product label, field measurement or installation instruction.

Open the original full-size SVG

The panel label and the electrician / authority having jurisdiction decide.

Sources: Q7 Square D 1100CT0501 pp.33-34, 60; S10 Murray 4810366 Rev. D p.1; S1 Siemens letter 2019-09-05 pp.1-2 (copy linked from the Siemens Sandy FAQ); E1 Eaton IL00304001Y p.1;

S4 Siemens QD brochure p.2; Q1 Square D FAQ FA109246; Q4 Square D 0700DB2001; C3, C7, C8, C10 CPSC notices. This chart lists documents to read; it is not installation guidance.

The chart

Each row cites the source ID and page; full titles are in the source list at the bottom.

#PanelEraBreaker family (document wording)Source & pageFlag
M01Square D QO (QO/NQO/NQOD/NQ panelboards)current and legacySquare D QO (plug-on)Q3 FA124299; Q1 FA109246
M02Square D Type QO loadcenters (Eaton heading: "Replacement Breakers for Square D Type QO Loadcenters")current and legacyEaton CHQ 3/4-inch (CHQ115-CHQ150 1P; CHQ215-CHQ260 2P)E2 p.V1-T1-102 (CHQ115-CHQ150 1P, CHQ215-CHQ260 2P); E12 p.V1-T1-102 (same table); E3 p.3 (prints CHFQ115-CHFQ150 / CHFQ215-CHFQ250)X1 X3
M03Square D QO load centers (only those on QD list)current and legacySiemens Type QD (D115-D160 1P; D215-D260 2P)S4 p.1-2 (panel list p.2); S5; S6 pdf p.39; S9 p.47 (2025 web edition repeats QD as UL Classified for specific Square D load centers; compatibility list packaged with each breaker)X1
M04Specific Square D load centers (S6 p.61: Type MSQ UL Classified)legacy (S2 p.1: "Murray Mini Circuit Breaker" phased out December 2019)Murray Type MSQ (MQ115-MQ160; MQ215-MQ260)S6 pdf p.61; S2 p.1 (phase-out)X1
M05Square D Homeline (HOM)current and legacySquare D Homeline HOMQ1 FA109246; Q2 FA129931
M06Square D Homeline (catalog numbers printed on Eaton list IL00304001Y)current and legacyEaton CL115-CL150 / CL215-CL250 (replace HOM115-HOM250); CL115GFT-CL130GFT (replace HOM115GFI-HOM120GFI); CL115AF-CL120AF (replace HOM115AFI-HOM120AFI); CL115CAF-CL120CAF, CLCAF115-CLCAF120, CLAF115 and CLAF120 (replace HOM115CAFI-HOM120CAFI); CLDF115-CLDF120 (replace HOM115DF-HOM120DF)E1 p.4 replacement tables; E1 p.10 (Square D panelboards), p.3 (CLCAF-specified panelboards), p.2 (Square D meter centers); E3 p.3; E2/E12 p.V1-T1-103 (heading and standard CL115-CL150 / CL215-CL250 only); K4X1 X4
M07Square D Homeline panelanySquare D QO breakers: "only UL tested and approved for use in QO, NQO, NQOD, and NQ panelboards" (Q3)Q3 FA124299 (QO only in QO/NQO/NQOD/NQ)
M08Square D QO or Homeline panelanySquare D: QO and Homeline load centers are "UL tested, listed, and labeled to accept ONLY Square D circuit breakers"; other manufacturers' breakers "VOID" the UL listing and warranty (Q1)Q1 FA109246X1
M10Panels manufactured before 1968 with unnotched stabs (Siemens and Eaton catalog notes)legacySiemens QT duplex Q1515NC-Q3030NC and Murray MH-T duplex MP1515N-MP3030N (footnote "a": "Non-CTL. For replacement use only in panels manufactured before 1968"); Eaton Non-CTL duplex Type BR (BR1515-BR3050) and Type BRD quadplex ("For replacement in enclosures manufactured prior to 1968 with unnotched stabs. Circuit breakers do not have rejection tab.")S6 PDF p.37 (QT duplex footnote "a") and PDF p.58 (Murray MH-T duplex footnote "a"); E12 p.V1-T1-83 (Non-CTL duplex Type BR) and p.V1-T1-78 (Type BRD); S9 p.45 (same Non-CTL footnote, page revised 08/31/22)
M11ITE / Siemens panelboards (catalog nos. on Eaton list)current and legacyEaton CL (replace Q115-Q250); CL115GFT-CL130GFT (replace QF115-QF130); CL115AF-CL120AF (replace Q115AF-Q120AF); CL115CAF-CL120CAF, CLCAF115-CLCAF120, CLAF115 and CLAF120 (replace Q115AFC-Q120AFC per E1; QF115AFC-QF120AFC per E3); CLDF115-CLDF120 (replace Q115DFP-Q120DFP per E1; Q115DF-Q120DF per E3)E1 p.4 replacement tables; E1 pp.5-7 (ITE/Siemens panelboards; heading "CLDF115, CLDF120" printed on p.5; pp.6-7 print no Eaton type heading) and p.3 (Siemens meter centers, under CL headings); E3 p.3; K4X4 X10
M13Murray Meter Combo, EQ Small Circuit, Rock Solid load centersmanufactured after January 2002Siemens equivalents per cross-reference: MP-T/MP-HT/MP-MT->QP/QPH/HQP; MH-T->QT; MP-GT->QPF/QPF2; MP-AT2->QAF2; MP-GAT2->QFGA2; MP-ET->QE; MSQ->QD; MD-T->QN; MPP->QPPS1 p.1 and p.2 table; S2 p.1X12
M14Murray load centersmanufactured prior to January 2002 (S1 p.1)Siemens letter: "refer to the wiring diagram affixed to the inside of the door of the loadcenter for the specific breaker types that are approved for that panel" (S1 p.1)S1 p.1; S10 p.1 ("Refer to wiring diagram label on inside of load center door or cover for product ratings, acceptable components")
M15Murray panelboards/meter centers (catalog nos. on Eaton list)legacyEaton CL (replace MP115-MP250); CL115GFT-CL130GFT (replace MP115GF-MP130GF); CL115AF-CL120AF (replace MP115AF-MP120AF); CL115CAF-CL120CAF, CLCAF115-CLCAF120, CLAF115 and CLAF120 (replace MP115AFC-MP120AFC); CLDF115-CLDF120 (replace MP115DF-MP120DF)E1 p.4 replacement tables; E1 p.9 ("Crouse-Hinds/Murray Listed Panelboard Catalog Numbers"; no Eaton type heading printed) and p.3 (Murray meter centers, under CL headings); E3 p.3; K4X4 X6
M16Murray (any)S2 p.1: "Murray Mini Circuit Breaker" and "Murray Electronic Breakers" phased out December 2019Original Murray MP-T familyS2 p.1
M17Crouse-Hinds (E1 p.9 heading "Crouse-Hinds/Murray Listed Panelboard Catalog Numbers")legacyEaton CL115-CL150 / CL215-CL250 (replace Crouse-Hinds MP115-MP150 / MP215-MP250)E1 p.4 standard table; E1 p.9; E3 p.3 standard table; K4
M19GE load centers (G1 p.1: "ReliaHome, PowerMark Pro, and PowerMark Gold load centers")current and legacyGE/ABB "standard 1\" THQL"; THQLT tandem; THQLQ quad (G1 pp.1-2)G1 p.1-3; G2 p.1; G3 p.2
M20GE load centers with 1/2-inch provisionslegacyGE THQP 1/2-inchG1 p.1 and p.3 (no new orders after 2024-10-02; obsolete 2024-12-31); G2 p.1
M21ABB ReliaHome load centersOct 2024 onwardABB THQL, THQLT, THQLQ; NOT THQPG1 p.1; G3 p.2
M22GE panelboards/meter centers (catalog nos. on Eaton list)current and legacyEaton CL (replace THQL1115-THQL2150); CL115GFT-CL130GFT (replace THQL1115GF-THQL1130GF); CL115AF-CL120AF (replace THQL1115AF-THQL1120AF); CL115CAF-CL120CAF, CLCAF115-CLCAF120, CLAF115 and CLAF120 (replace THQL1115AF2-THQL1120AF2); CLDF115-CLDF120 (replace THQL1115DFP-THQL1120DFP per E1; THQL1115DF-THQL1120DF per E3)E1 p.4 replacement tables; E1 p.8 (GE panelboards; no Eaton type heading printed) and p.2 (GE meter centers, under CL headings); E3 p.3; K4X2 X4 X10
M23Thomas & Betts (catalog numbers printed on Eaton list IL00304001Y)legacyEaton CL (replace TB115-TB250); CL115GFT-CL130GFT (replace GFB115-GFB130)E1 p.4 replacement tables; E1 p.10 (T&B panelboards); E3 p.3; K4
M24Eaton / Cutler-Hammer Type CHcurrentEaton Type CH (3/4-inch)E5 PDF p.5 (Type CH: 3/4-inch; "Exclusively for Eaton type CH loadcenters"; lifetime warranty); K5 (Eaton KB 000015509: 3/4-inch, black body with tan handle, trips to OFF, 10 kAIC only, CHT twin universal CTL/non-CTL, limited lifetime warranty)X11
M25Eaton Type BRcurrentEaton Type BR (1-inch)E5 PDF p.5 (Type BR: 1-inch; trips to center position; 10-year warranty); K5 (1-inch, trips to center, 10-65 kAIC on selected amps, duplex/quadplex CTL and non-CTL, limited 10-year warranty); K3 (only BR breakers designed, tested and UL listed for BR load centers); K6 (Eaton KB 000006519: "BR breakers are UL approved to be used in the following loadcenters: Westinghouse, Challenger, Bryant, Cutler-Hammer, and Eaton BR loadcenters.")
M26Westinghouse, Challenger, Bryant loadcenterslegacyEaton Type BRE5 PDF p.5 ("BR breakers are UL approved genuine replacement breakers for loadcenters made by Westinghouse, Challenger, and Bryant"); K5 ("UL listed to go in Bryant, Cutler-Hammer BR, Challenger and Westinghouse loadcenters"); K6 (Eaton KB 000006519: "BR breakers are UL approved to be used in the following loadcenters: Westinghouse, Challenger, Bryant, Cutler-Hammer, and Eaton BR loadcenters.")X7
M27Eaton BR loadcentersanyEaton: "CL breakers are not UL listed to be used in BR loadcenters" (K3)K3 (Eaton KB 000001492)
M30Federal Pacific Stab-Lok (thick NA / thin NC)legacyConnecticut Electric UBIFCE1 pdf pp.7-8 (catalog pp.2-3) and PDF p.2; CE2 p.1-2; P1 (UL Product iQ abridged DIXF search 2026-11-15: 5 entries, Eaton x4 and Siemens x1)X8
M31ZinscolegacyConnecticut Electric UBIZCE1 pdf pp.10-11 (catalog pp.5-6); P1 (UL Product iQ abridged DIXF search 2026-11-15: 5 entries, Eaton x4 and Siemens x1)X8
M32PushmaticlegacyConnecticut Electric UBIPCE1 pdf p.9 (catalog p.4); CE2; P1 (UL Product iQ abridged DIXF search 2026-11-15: 5 entries, Eaton x4 and Siemens x1)X8
M33WadsworthlegacyConnecticut Electric UBIACE1 pdf p.12 (catalog p.7); P1 (UL Product iQ abridged DIXF search 2026-11-15: 5 entries, Eaton x4 and Siemens x1)X8
M34Challenger Type A panelslegacyConnecticut Electric UBITB Type A (half-width L/R clip)CE1 pdf p.6 (catalog p.1); P1 (UL Product iQ abridged DIXF search 2026-11-15: 5 entries, Eaton x4 and Siemens x1)X8
M35Challenger loadcenterslegacyEaton Type BR (K6: "BR breakers are UL approved to be used in the following loadcenters: Westinghouse, Challenger, Bryant, Cutler-Hammer, and Eaton BR loadcenters.")E5 PDF p.5; K5; K6X7
M36UL Classified breakers (any panel)anyEaton: Classified breakers "can be used in applications up to and including 120/240 volts, 225 ampere (A) panels"; available short-circuit current "cannot exceed" 10 kA (E4 p.2). UL: 120/240 V, 10 kA or less (U1). Eaton brochure: "for use with panelboards rated 225 amperes, are limited to 120/40 [sic] volt applications" (E3 p.2)U1 items 97-98; E4 p.2; E3 p.2
M37Square D QO / QOBanyCounterfeit breakers marked "Square D" (CPSC recalls); genuine-breaker cues per CPSC: "the amp rating written on the handle in white paint", "the Square D insignia molded onto the breaker side", yellow chromate mounting clip; "authentic Square D circuit breakers manufactured prior to 2003 did not have white paint on the amperage numbers" (C16)C5; C6; C14; C15; C16; C9 (general CPSC counterfeit warning)
M38Siemens / Murray breakers, load centers and a meter combo (CPSC recall 10-354, Sept 23, 2010)breaker date codes 0610 / 0710; load centers and meter combo made June 23 - August 25, 2010 (C3)Siemens/Murray 15-50 A breakersC3
M39Square D QO Plug-on-Neutral load centersmade 2020-02 to 2022-01 (date codes 200561-220233)n/a (panel recall)C8
M41American Switch, Arrow-Hart, General Switch, GTE/Sylvania loadcenterslegacyEaton Type BRK5 (Eaton KB 000015509: "Not UL listed but 'fits' in American Switch, Arrow-Hart, General Switch, GTE/Sylvania loadcenters")
M42Eaton BR / CH loadcenters (Class CTL)currentEaton BD duplex, BQ/BQC quadplex (CTL, rejection tab); CHT twin universal CTL/non-CTLE12 p.V1-T1-91 (Class CTL: BD, BQ, BQC and CHT have UL listed rejection tab; OEM interiors have notched stabs); E12 p.V1-T1-68 (BD/BQ/BQC in CTL listed BR loadcenters; BR twin in Non-CTL BR loadcenters); E12 p.V1-T1-37 (CHT suitable for CTL and non-CTL CH loadcenters)
M43ITE load centers installed Sep 1986 - May 1987 (date codes H2586-H3186, J0186-J3086, K0186-K2486)1986-1987n/a (panel inspection program)C10 (CPSC recall page, recall number 88-091, Recall Date November 01, 1988)
M44GE TSLR1220CSAL meter socket load centers (date codes "SAL421 through 432") and Midwest R256EB1A/R256EB1NA/R256EB1018Amade May - Aug 6, 2004n/a (panel recall)C13 (CPSC recall 05-515, 2004-11-19)
M45Square D QO load centers (ABB wording: "*Square D **QO Load Centers")ABB BuyLog Section 1, "Section Updated 09/2026" (G4 p.1-3)ABB Type TQ 3/4": TQ1115, TQ1120, TQ1130, TQ1140, TQ1150 (1-pole); TQ2115, TQ2120, TQ2130, TQ2140, TQ2150, TQ2160 (2-pole)G4 p.1-57 ("3/4" UL Classified Circuit Breakers for use in *Square D **QO Load Centers."; "10 kAIC RMS symmetrical")X1
M46ABB ReliaHome T-Series load centers (ordering-code position "Q")ABB BuyLog Section 1, "Section Updated 09/2026" (G4 p.1-3)THQL / THHQLG4 p.1-18 (T-Series ordering-code legend for "Q": "For use with THQL/THHQL circuit breakers only")
M47ABB wording: "ABB and GE load centers, meter combos, modular metering, enclosed circuit breakers, Midwest single socket metering, and Midwest RV power pedestals"ABB BuyLog Section 1, "Section Updated 09/2026" (G4 p.1-3)ABB Q-line plug-in: Type THQL 1–inch module (10,000 AIC), Type THHQL 1–inch module (22,000 AIC), Type TXQL 1–inch module (65,000 AIC)G4 p.1-49 ("Q-line plug-in circuit breakers are designed for use in ABB and GE load centers, meter combos, modular metering, enclosed circuit breakers, Midwest single socket metering, and Midwest RV power pedestals")
M48GE PowerMark Plus three-phase 120/208 V load centres (Canadian CSA guide)ABB CSA selection guide 1SXP901001C0201, March 2020 (G5 back cover)1” THQLG5 p.5 / PDF p.7 ("3ph 120/208V Load Centre only accepts 1” THQL style breakers.")
M49GE PowerMark single-phase 120/240 V load centres (Canadian CSA guide)ABB CSA selection guide 1SXP901001C0201, March 2020 (G5 back cover)"Maximum Circuits" columns for 1” THQL and 1/2” THQP; main-lug TLC4222CCA footnote 4: "Accepts 1” THQL breakers only"G5 p.3 / PDF p.5
M50Siemens panelboards, or other products, designating the use of the Siemens circuit breaker types (S11 p.2 wording)UL LLC letter dated 2020-02-11 (S11 p.1)Murray types per S11 p.1 table: MP-AT2 / MP-HAT2 / MP-MAT2 (QAF2 / QAFH2 / HQAF2); MP-AT / MP-HAT (QAF / QAFH); MP-GAT2 / MP-HGAT2 / MP-MGAT2 (QFGA2 / QFGAH2 / HQFGA2); MP-T (QP); MH-T (QT); MPP-T / MPP-HT / MPP-MT / MPP-PT (QPP / QPPH / HQPP / HQPPH); MP-GT2, MP-HGT2, MP-MGT2 (QPF2, QPHF2, HQPF2); MP-ET2, MP-HET2 (QE2, QEH22 as printed)S11 p.1 table; S11 p.2 ("The Murray circuit breaker types, manufactured by Siemens, may be used or are suitable replacements in Siemens panelboards, or other products, designating the use of the Siemens circuit breaker types.")X12

What the documents disagree on

  • Does a Classified breaker void a Square D panel's listing or warranty?
    • Square D says QO and Homeline load centers are listed to accept only Square D breakers, and that other manufacturers' breakers void the UL listing and warranty [Q1].
    • Its residential warranty: "Schneider Electric disclaims all liability for damage, injury or non-performance caused by the use or failure of incompatible or UL® classified circuit breakers." [Q4 p.1]
    • Eaton says its Classified breakers comply with NEC 110.3(B) and are UL listed for specific loadcenters [E4 p.1].
    • We show both positions and do not decide between them. Ask Square D about the warranty, and your AHJ about code compliance.
  • Eaton's own naming changes between editions.
    • GE breakers are written "THQ" in an older Eaton chart (file metadata 2011) [E0] and "THQL" in the 2024 list and 2026 brochure [E1 p.4] [E3 p.3].
    • Eaton's QO-replacement line appears as CHQ in the catalog [E2 p.V1-T1-102] and as CHFQ in the 2026 brochure [E3 p.3].
    • We quote each document's catalog numbers exactly as printed.
  • Third-party "Classified" wording. Connecticut Electric's catalog describes its UBI breakers as "Safety Agency Certified to UL489" [CE1 PDF p.2]. UL's public Product iQ search for the Classified category DIXF, run on 2026-11-15, returned five entries: four Eaton files and one Siemens file [P1]. Separately, CPSC records that Connecticut Electric, acting as a distributor, recalled about 64,000 counterfeit "Square D" QO and QOB breakers in 2007 [C14].

Era cut-offs that change the answer

DateWhat changesSource
Before 1968Siemens and Murray catalogs mark some space-saver breakers "Non-CTL… for replacement use only in panels manufactured before 1968"[S6 PDF p.37, p.58]
January 2002"All Murray Meter Combo Load Centers, EQ Small Circuit Load Centers, and Rock Solid Load Centers manufactured after January 2002 may use Siemens brand circuit breakers."[S1 p.1]
December 2019 – fall 2020Murray phase-out table: December 2019 = "Murray Mini Circuit Breaker", "Murray Electronic Breakers", "Meter Combos", "EQ Small Circuit Load Centers"; Summer 2020 = "Murray Rock Solid Load Centers"; Fall 2020 = "Murray Sockets"[S2 p.1]
2 October 2024 / 31 December 2024GE/ABB ½-inch THQP: no new orders / obsolete; ABB ReliaHome load centers do not accept THQP[G1 p.1, p.3]

Recalls to check first

ProductIdentifiersSource
Siemens & Murray 15–50 A breakers, some load centers and a meter combo (about 2.2 million units)Breakers: date code 0610 or 0710; load centers and meter combo: made June 23 – August 25, 2010; listed catalog numbers Q115, Q120, Q130, Q215, Q230, Q250, MP115, MP115U, MP120, MP130, MP215, MP230, MP230U, MP250[C3]
Square D QO Plug-on-Neutral load centers (about 1.4 million)Date codes 200561–220233[C8]
Square D QO/Homeline AFCI breakers (about 700,000)See notice for date codes[C7]
Siemens/Murray 2-pole GFCI breakers (about 144,000)Sold March 1996 – April 1998[C4]
Challenger HAGF-15/HAGF-20 GFCI breakersMade 22 Feb – 29 Apr 1988[C2]
Counterfeit "Square D" QO/QOB breakers (several recalls, 2006–2010)Genuine QO cues listed by CPSC: white amp rating on the handle, molded Square D insignia, yellow chromate clip [C5] [C6] [C14] [C15]. One notice adds: "authentic Square D circuit breakers manufactured prior to 2003 did not have white paint on the amperage numbers" [C16][C5] [C6] [C14] [C15] [C16]
I-T-E load centers installed Sep 1986 – May 1987 (Siemens inspection program, 1988)Date codes H2586–H3186, J0186–J3086, K0186–K2486 at the top of the wiring diagram label; "inspected lugs" stamp means already inspected[C10]
GE TSLR1220CSAL and Midwest meter socket load centers (2,754 units, 2004)Date codes SAL421–432; made May – Aug 6, 2004[C13]
Square D Series 1 two-pole GFCI breakers, 15–30 A (1988 replacement program)See notice[C11]
Eaton MBED3042 meter breakers (about 1,100, 2014)MBED3042B200BF, MBED3042B200BF6, MBED3042B225PV, MBED3042PV200BF[C17]

Federal Pacific Stab-Lok: in 1983 CPSC "closed the matter without making a determination as to the safety of FPE circuit breakers" [C1].

Common confusions

  • "Eaton BR fits, so it's fine in my Siemens/Murray panel."
    • Eaton's classified line for other makers' panels is Type CL, not BR [E2 p.V1-T1-103] [E1].
    • Eaton describes BR as the replacement for Westinghouse, Challenger and Bryant loadcenters [E5 PDF p.5].
    • Eaton's knowledge base: BR is "Not UL listed but 'fits'" in American Switch, Arrow-Hart, General Switch and GTE/Sylvania loadcenters [K5].
  • "Eaton CL is just a BR for any panel." Eaton says CL is not UL listed for its own BR loadcenters [K3].
  • "Same amp rating means compatible." UL's compatibility list ties a Classified breaker to specific panel catalog numbers and supply limits [U1 item 99].
  • "Any Murray panel takes Siemens."
    • Siemens' letter names Murray Meter Combo, EQ Small Circuit and Rock Solid load centers "manufactured after January 2002" [S1 p.1].
    • For products made before that date it says to "refer to the wiring diagram affixed to the inside of the door of the loadcenter" [S1 p.1].

FAQ

Questions taken from search-engine question data (Google autocomplete and "People also ask" boxes) recorded on 2026-11-15 for eight target queries (raw/serp/paa_2026-11-15.txt). We answer a question only where a manufacturer, UL or CPSC document covers it.

Does the breaker brand have to match the panel brand?
Eaton's catalog describes two routes: specified breakers, which "are listed by the manufacturer of the panelboard for use in a particular panel", and Classified breakers "for use in place of the breakers specified on the panelboard" [E2 p.V1-T1-101]. UL ties a Classified breaker to the panelboards on its compatibility list [U1 items 97–99]. Square D states that non-Square D breakers void its load centers' listing and warranty [Q1].

What is a compatibility list?
UL describes it as a publication supplied with a Classified breaker. It lists the breaker's catalog numbers and ratings, the listed panelboards it may be used in, the breakers it replaces, and the maximum voltage and available short-circuit current [U1 item 99].

Are Classified breakers allowed in 200 A or 400 A panels?
Eaton states its Classified breakers can be used "in applications up to and including 120/240 volts, 225 ampere (A) panels" [E4 p.2].

What do CTL and Non-CTL mean?
Eaton's catalog: "Paragraph 384.15 requires branch circuit panelboards to be provided with physical means to prevent the installation of more overcurrent devices than that number of which the enclosure was designed, rated and approved. Class CTL Duplex, Quadplex and twin breakers (identified by a catalog number prefix BD, BQ, BQC and CHT) are equipped with a UL listed rejection tab over the line terminal. All OEM interiors have appropriately notched stabs to accept these rejection tab Class CTL breakers. Duplex, Quadplex and twin breakers manufactured without the rejection tab (identified by a catalog number prefix BR, BRD and CHT) are available for replacement purposes in older interiors." [E12 p.V1-T1-91] Siemens' and Murray's catalogs footnote certain duplex breakers "Non-CTL. For replacement use only in panels manufactured before 1968" [S6 PDF p.37, p.58].

Where do I find my panel's catalog number?
CPSC's 2010 Siemens recall release says: "The catalog number for the load centers and meter combos is printed on a label inside the metal box door and on the packaging" [C3]. Murray's instruction sheet likewise points to the wiring diagram label inside the door or cover for product ratings and acceptable components [S10 p.1].

What brand breakers are compatible with Square D?
The makers disagree, so both sides are shown. Square D says its QO and Homeline load centers are UL tested, listed and labeled to accept only Square D breakers, and that other makers' breakers void the UL listing and warranty [Q1]. Eaton prints "Type CHQ Replacement Breakers for Square D Type QO Loadcenters" [E2 p.V1-T1-102], and Siemens describes Type QD as UL Classified for specific Square D load centers [S6 PDF p.39] [S9 p.47].

Are Eaton, Westinghouse, Square D and Cutler-Hammer breakers compatible?
Eaton says its BR breakers are UL approved for Westinghouse, Challenger, Bryant, Cutler-Hammer and Eaton BR loadcenters [K6]. For Square D, Eaton prints "Type CHQ Replacement Breakers for Square D Type QO Loadcenters" [E2 p.V1-T1-102], while Square D says only Square D breakers keep its QO and Homeline listing [Q1]. Eaton's ¾-inch CH is only for CH loadcenters [E5 PDF p.5].

Will Eaton BR breakers fit a Square D panel?
Eaton: "BR breakers are UL approved to be used in the following loadcenters: Westinghouse, Challenger, Bryant, Cutler-Hammer, and Eaton BR loadcenters." [K6] Square D: its QO and Homeline load centers are "UL tested, listed, and labeled to accept ONLY Square D circuit breakers" [Q1].

Sources

IDPublisherDocument / versionLinkKind
E0Eaton (hosted on Home Depot CDN)SA00304001E UL Classified Circuit Breaker Replacement Chart (PDF mod 2011-05-10), olderURL not recorded (Home Depot thdstatic CDN copy; obtained 2026-11-15 in research/directions/2026-11-15-new)primary-mirror
E1EatonIL00304001Y, visible imprint "Revised September 2024" (p.10); hidden text layers also contain "Revised May 2024" and REV. 24/27 markers; PDF mod 2025-06-05, 10 pplinkprimary
E2EatonCA08100002E, Nov 2022 (PDF mod 2024-12-30), pp V1-T1-101..105linkprimary
E3EatonBR003051EN (URL br003034en), July 2026, 4 pplinkprimary
E4EatonWP003005EN, May 2024, 2 pplinkprimary
E5EatonMZ00400002E (PDF mod 2025-06-13), 44 pplinkprimary
E12EatonCA08100002E Volume 1 Residential and Light Commercial, November 2022, full 105 pp (PDF created 2022-11-02); captured 2026-11-15linkprimary
K3Eaton Knowledge HubArticle 000001492 "Can CL breakers be used in BR loadcenters?", printed 2026-11-15linkprimary
K4Eaton Knowledge HubArticle 000011287 "Eaton replacement circuit breaker that fits in a Siemens loadcenter", printed 2026-11-15linkprimary
K5Eaton Knowledge HubArticle 000015509 "Major differences between BR and CH breakers", printed 2026-11-15 (right edge of table truncated in print)linkprimary
K6Eaton Knowledge HubArticle 000006519 "Which loadcenters can BR breakers be installed in?", printed 2026-11-15 (no article date shown)linkprimary
S1Siemens Industry (copy linked from the Siemens Sandy FAQ page S3)letter dated 2019-09-05, 2 pplinkprimary-mirror
S2Siemens Industry (copy linked from the Siemens Sandy FAQ page S3)letter dated 2019-09-05, 2 pplinkprimary-mirror
S4Siemens (cache.industry.siemens.com)SIE_BR_QD (PDF mod 1999-06-05), 2 pplinkprimary
S5Siemens (distributor mirror: Winsupply)same content as S4 (PDF mod 2008-04-24), 2 pplinkprimary-mirror
S6Siemens IndustrySPEEDFAX 2017 Section 1 Load Centers & Circuit Breakers (PDF mod 2020-02-13), 66 pplinkprimary
S9Siemens IndustrySPEEDFAX Section 1 Load Centers & Circuit Breakers, web edition SF-17-Sect-01-ALL (PDF created 2025-01-29; pages individually revised 2020-03 to 2025-01), 56 pplinkprimary
S10Siemens Industry / Murray Electrical ProductsInstallation instructions "Single Phase Load Centers 12 thru 42 Circuits", 4810366 Rev. D, (c) 2009 (PDF created 2018-01-05), 4 pp image-only (OCR in raw/ocr/)linkprimary
S11UL LLC (letter to Siemens Industry, Inc.; hosted on Siemens Industry Online Support)UL LLC letter dated 2020-02-11, subject "Murray Breaker Types Used in Siemens Equipment", Our Reference File E82615, E82617, E160869 and E468786, Project Number 4789379155; 2 pp image-only (OCR and visual check in raw/ocr/); captured 2026-11-16linkprimary
Q1Schneider Electric / Square DFAQ FA109246, fetched 2026-11-15linkprimary
Q2Schneider Electric / Square DFAQ FA129931, fetched 2026-11-15linkprimary
Q3Schneider Electric / Square DFAQ FA124299, fetched 2026-11-15linkprimary
Q4Schneider Electric / Square DData bulletin 0700DB2001 (PDF mod 2020-07-24), 2 pplinkprimary
Q7Schneider Electric / Square DCatalog 1100CT0501 "Square D QO and Homeline Load Centers and Enclosures", 06/2026 (footer Rev.03), 88 pp; printed page = PDF page; captured 2026-11-15linkprimary
G1ABB Electrification USLCM announcement 2024-06-28, ABB document 1TQC114500E0003, 3 pplinkprimary
G2ABB (hosted on Home Depot CDN)PDF mod 2025-05-28, 2 pplinkprimary-mirror
G3ABB (hosted on Home Depot CDN)compatibility letter rev A 2025-05-22, 2 pplinkprimary-mirror
G4ABB Electrification USBuyLog Section 1 "Load centers, meter combos, and residential circuit breakers", document 9AKK108467A9432, "Section Updated 09/2026" (p.1-3), 72 pp; printed page 1-N = PDF page N; captured 2026-11-16linkprimary
G5ABB (Canada)"GE PowerMark Gold Load Centres CSA Selection Guide", 1SXP901001C0201, March 2020 (back cover), 16 pp; Canada / CSA; printed page n = PDF page n+2linkprimary
U1UL SolutionsMCCB Marking and Application Guide (web), fetched 2026-11-15linkprimary
P1UL Solutions Product iQ (abridged, no login)Search "DIXF", captured 2026-11-15linkprimary
C1U.S. CPSCnews release 1983-03-03, revised 2011-02-18linkprimary
C2U.S. CPSCrecall 1988-11-12linkprimary
C3U.S. CPSCrecall 2010-09-23linkprimary
C4U.S. CPSCrecall 1998-10-07linkprimary
C5U.S. CPSCrecall 2010-08-02linkprimary
C6U.S. CPSCrecall 2006-11-16linkprimary
C7U.S. CPSCrecall 2004-11-03linkprimary
C8U.S. CPSCrecall 2022-06-16linkprimary
C9U.S. CPSCnews release May 2007linkprimary
C10U.S. CPSCcpsc.gov recall web page, Recall Date November 01, 1988, recall number 88-091; printed to PDF in browser 2026-11-16, 4 pplinkprimary
C11U.S. CPSCcpsc.gov recall web page, Recall Date April 13, 1988, recall number 88-022; Units "Approximately 80,000"; printed to PDF in browser 2026-11-16, 4 pplinkprimary
C13U.S. CPSCcpsc.gov recall web page, Recall Date November 19, 2004, recall number 05-515; printed to PDF in browser 2026-11-16, 4 pplinkprimary
C14U.S. CPSCcpsc.gov recall web page, Recall Date October 30, 2007, recall number 08-054; printed to PDF in browser 2026-11-16, 4 pplinkprimary
C15U.S. CPSCcpsc.gov recall web page, Recall Date December 27, 2007, recall number 08-151; printed to PDF in browser 2026-11-16, 4 pplinkprimary
C16U.S. CPSCcpsc.gov recall web page, Recall Date May 27, 2008, Release #08-286; printed to PDF in browser 2026-11-16, 5 pplinkprimary
C17U.S. CPSCcpsc.gov recall web page, Recall Date December 02, 2014, recall number 15-710; printed to PDF in browser 2026-11-16, 4 pplinkprimary
CE1Connecticut Electric2017 catalog (PDF mod 2017-09-12), 32 pplinkprimary (vendor)
CE2Connecticut ElectricUBI cut sheet (PDF mod 2005), 2 pplinkprimary (vendor)

All documents fetched 2026-11-15 or 2026-11-16 and archived with SHA256 (see SOURCE-LIBRARY.csv). Kind: primary = issued by the manufacturer/agency; primary-mirror = manufacturer document hosted by a third party.

Related reference photographs
An open breaker panel.
An open breaker panel. This example does not identify your equipment.
Photo credit and licence

"Eaton circuit breaker panel open.JPG" by BrokenSphere, licensed CC BY-SA 3.0 (https://creativecommons.org/licenses/by-sa/3.0), via Wikimedia Commons: https://commons.wikimedia.org/wiki/File:Eaton_circuit_breaker_panel_open.JPG Resized for the web.

Original Commons file and licence

Keep the reference with your question.

Retain the exact identifier, document revision, page and unresolved conditions. The lookup covers only one Eaton list; a result is not an equipment or installation assessment.

Search Eaton’s document Record a source discrepancy