GE: distinguish the family and the market.

Compare THQL and THQP, dated ABB notices and the Canadian selection guide without treating them as the same document or market.

Quick answer

GE residential load centers and GE THQL breakers are now branded ABB [G3 p.2].

  • THQL, THQLT (tandem) and THQLQ (quad): ABB says they are compatible with GE PowerMark and ABB ReliaHome load centers [G3 p.2] [G1 p.1].
  • ½-inch THQP: entered ABB's classic phase on 28 June 2024. No new orders were accepted from 2 October 2024, and it became obsolete on 31 December 2024. The new ReliaHome load centers do not accept THQP [G1 p.1, p.3].
  • Eaton Type CL is UL Classified to replace THQL1115–THQL1150 and THQL2115–THQL2150 in the GE panelboards and meter centers on Eaton's list [E1 p.4] [E1 p.2, p.8].
Residential breaker families: width and trip indication as the makers state them

Compare a printed dimension, not an installation permission. Equal width does not establish a listed or classified combination.

Eaton CH3/4 in. per poleE5 p.5
Eaton BR1 in. per poleE5 p.5
Eaton CL1 in. per poleE12 p.103
Eaton CHQ3/4 in. per poleE5 p.8
Square D QO3/4 in. per poleQ7 p.67
Square D Homeline1 in. per poleQ7 p.67
Siemens QP1 in. per poleS9 p.1
Siemens QD3/4 in. per poleS9 p.47
GE / ABB THQL1 in. per poleG1 p.1
GE / ABB THQP1/2 in. per poleG1 p.1
Original drawing and source annotations

The original drawing is schematic, not a product label, field measurement or installation instruction.

Open the original full-size SVG

"½" THQP"; ABB not accepting new orders as of October 2, 2024

Sources: E5 Eaton Residential Product Guide MZ00400002E p.5, p.8; K5 Eaton KB 000015509; E12 Eaton CA08100002E (2022) p.103; E1 Eaton IL00304001Y p.1; Q6 Square D 0730CT9801 p.3;

Q7 Square D 1100CT0501 pp.45, 67; S9 Siemens SPEEDFAX SF-17 pp.1, 47; S4 Siemens QD brochure p.1; G1 ABB THQP notice (June 28, 2024) p.1. The panel label governs.

Two fictional breaker-like housings each with a separate blank document folder.
AI-generated concept illustration. Keep each family’s source statement separate. These generic objects do not depict Siemens, GE, Eaton or Square D products or establish an interchangeability claim. Not technical evidence.

GE / ABB compatibility table

PanelEraBreaker familySourceLimits / notes
GE PowerMark load centers (single-phase)current and legacyTHQL 1-inch; THQLT tandem; THQLQ quad[G1 p.1] [G2 p.1] [G3 p.2]ABB: tandem fits any 1-inch space; quad uses two 1-inch spaces in an existing GE or new ABB load center [G2 p.1]
ABB ReliaHome load centersOctober 2024 onTHQL, THQLT, THQLQ; not THQP[G1 p.1] [G3 p.2]
ABB ReliaHome T-Series load centersBuyLog Section 1, "Section Updated 09/2026" [G4 p.1-3]THQL / THHQL[G4 p.1-18]Ordering-code legend for the "Q" position: "For use with THQL/THHQL circuit breakers only" [G4 p.1-18]
"ABB and GE load centers, meter combos, modular metering, enclosed circuit breakers, Midwest single socket metering, and Midwest RV power pedestals" (ABB wording)BuyLog Section 1, "Section Updated 09/2026" [G4 p.1-3]Q-line plug-in: Type THQL (10,000 AIC), Type THHQL (22,000 AIC), Type TXQL (65,000 AIC), each a "1–inch module"[G4 p.1-49]"Q-line plug-in circuit breakers are designed for use in ABB and GE load centers, meter combos, modular metering, enclosed circuit breakers, Midwest single socket metering, and Midwest RV power pedestals" [G4 p.1-49]
GE PowerMark Plus three-phase 120/208 V load centres (Canadian CSA guide)guide dated March 2020 [G5 back cover]1” THQL[G5 p.5]"3ph 120/208V Load Centre only accepts 1” THQL style breakers." [G5 p.5]
GE PowerMark single-phase 120/240 V load centres (Canadian CSA guide)guide dated March 2020 [G5 back cover]"Maximum Circuits" columns for 1” THQL and 1/2” THQP[G5 p.3]Footnote 4 on main-lug TLC4222CCA: "Accepts 1” THQL breakers only" [G5 p.3]
GE load centers with ½-inch provisionslegacyTHQP ½-inch[G1 p.1, p.3] [G2 p.1]"THQP circuit breakers can only be used in ½" compatible GE load centers" [G2 p.1]
GE panelboards and meter centers on Eaton's listcurrent and legacyEaton CL (replaces THQL1115–THQL1150 and THQL2115–THQL2150); CL115GFT–CL130GFT (replaces THQL1115GF–THQL1130GF); CL115AF–CL120AF (replaces THQL1115AF–THQL1120AF); CL115CAF–CL120CAF, CLCAF115–CLCAF120, CLAF115 and CLAF120 (replace THQL1115AF2–THQL1120AF2); CLDF115–CLDF120 (replaces THQL1115DFP–THQL1120DFP)[E1 p.4; panel lists p.2, p.8]E1 p.1: "Single-Phase, 3-Wire, 120/240 V~", "Max. Available Short Circuit Current 10 kAIC"; E1 p.4 DANGER: "Do not use in series rated systems with those panelboards shown in this compatibility list" [E1 p.1, p.4]. Eaton's 2026 brochure prints the dual-function numbers as THQL1115DF–THQL1120DF [E3 p.3]

THQP → replacement map (from ABB's 2024 lifecycle notice)

ABB lists these replacement products for ½-inch THQP [G1 p.2]:

  • Tandems: THQLT1515, THQLT2020, THQLT1520 [G1 p.2].
  • Quads: THQLQ151515, THQLQ152015, THQLQ153015, THQLQ154015, THQLQ201520, THQLQ202020, THQLQ203020, THQLQ204020, THQLQ203015 [G1 p.2].
  • Standard 1-inch: THQL2145, THQL2150 and "THQL 1” breakers" [G1 p.2].
  • ABB's notice prints the THQP legacy list (THQP115…THQP250) beside the replacement list [G1 p.2].
ABB lifecycle phase for ½-inch THQPDateSource
Classic (announced)28 June 2024[G1 p.1, p.3]
Last time to buy / limited2 October 2024[G1 p.3]
Obsolete31 December 2024[G1 p.3]

ABB's UL Classified Type TQ for Square D QO load centers

  • ABB's BuyLog lists "TQ CIRCUIT BREAKERS": "3/4" UL Classified Circuit Breakers for use in *Square D **QO Load Centers." [G4 p.1-57]
  • Rating line: "10 kAIC RMS symmetrical" [G4 p.1-57].
  • Catalog numbers: TQ1115, TQ1120, TQ1130, TQ1140, TQ1150 (1-pole); TQ2115, TQ2120, TQ2130, TQ2140, TQ2150, TQ2160 (2-pole) [G4 p.1-57].
  • Square D says its QO and Homeline load centers are "UL tested, listed, and labeled to accept ONLY Square D circuit breakers" [Q1].

How to read a GE panel label

  • Find the load center catalog number (diagram D1).
  • Check whether the label or interior shows ½-inch (THQP) provisions. ABB notes THQP "could not be installed in every GE load center or in every space of a GE load center" [G2 p.1].
  • To compare against Eaton's Classified list, match the panel catalog number to IL00304001Y [E1].
Where your panel's own documents put the key facts

Keep the label and the document together.

Catalog numbers, breaker-type lists and dates are different fields. The actual label can use a different layout.

  1. Catalog number

    Record the complete identifier, including suffixes. Square D label samples, pp.33–34, 60

  2. Printed breaker types

    Keep the wiring-diagram label with the box label. Murray 4810366, p.1

  3. Date code

    Preserve the exact code when comparing an applicable notice. CPSC QO notice

Original drawing and source annotations

The original drawing is schematic, not a product label, field measurement or installation instruction.

Open the original full-size SVG

door of the panel" [C8]

Sources: Q7 = Square D catalog 1100CT0501 (06/2026) pp.33-34, 60 (label and wiring-diagram sample callouts); S10 = Murray/Siemens instructions 4810366 Rev. D pp.1-2; C10, C3, C8 =

CPSC recall notices (1988; 2010; 2022). The panel label and a licensed electrician decide what may be installed.

Era and series history

WhenEventSource
File metadata 2011An older Eaton CL chart refers to GE breakers as "THQ"[E0]
March 2020ABB Canada "GE PowerMark Gold™ Load Centres CSA Selection Guide", 1SXP901001C0201[G5 front cover; back cover]
September 2024Eaton's list IL00304001Y (revised September 2024) refers to "THQL"[E1 p.4, p.10]
28 June 2024ABB announces THQP classic phase[G1 p.1]
October 2024ABB launches ReliaHome; ReliaHome does not accept THQP[G1 p.1]
31 December 2024THQP obsolete[G1 p.3]
22 May 2025ABB compatibility letter (Rev. A): "GE Load Centers and GE THQL Circuit Breakers are now branded ABB"[G3 p.2]
September 2026ABB BuyLog Section 1: "Section Updated 09/2026"[G4 p.1-3]

Recalls and counterfeits

  • GE meter socket load centers (2004). CPSC, Midwest and GE recalled 2,754 meter socket load centers made from May through August 6, 2004: Midwest models R256EB1A, R256EB1NA and R256EB1018A, and GE model TSLR1220CSAL, date codes SAL421 through 432. Some were sold with loose internal bolt connections, which could cause excessive heat or fire [C13].
  • CPSC's general counterfeit-breaker warning [C9]. OSHA issued a separate alert about incorrectly refurbished Eaton/Cutler-Hammer E2 mining-series breakers [O1].

Common confusions

  • "THQP fits any GE panel." ABB says THQP can only be used in ½-inch-compatible GE load centers [G2 p.1].
  • "Tandem means THQP."
    • ABB lists THQLT tandems and THQLQ quads as replacement products for THQP [G1 p.2].
    • ABB says they "can be used in any GE or ABB load center" [G2 p.1].
    • The same ABB sheet says quads "can be installed in any (2) one-inch spaces" and, a few lines later, "utilize (2) two-inch spaces"; both wordings are printed [G2 p.1].
  • "Eaton's chart says THQ, so it doesn't cover THQL." An older Eaton chart (file metadata 2011) says THQ [E0]; the 2024 list and 2026 brochure say THQL [E1 p.4] [E3 p.3].

FAQ

What are GE breakers called now? ABB's 2025 compatibility letter says GE load centers and GE THQL breakers are now branded ABB [G3 p.2].

Do new ABB breakers fit my old GE panel? ABB says the new ABB breakers are backward compatible and lists THQL/THQLT/THQLQ as compatible with GE PowerMark [G3 p.2]. Your label governs.

Can I still buy THQP? ABB stopped accepting new THQP orders on 2 October 2024, and THQP became obsolete on 31 December 2024 [G1 p.1, p.3].

Can I use an Eaton CL breaker in a GE panel? Eaton's Type CL is UL Classified to replace THQL1115–THQL1150 and THQL2115–THQL2150 in the GE panelboards on its list [E1 p.4, p.8]. The panel catalog number must be listed. The limits are 120/240 V and 10 kA [U1 item 97].

Are GE and Square D breakers interchangeable? Square D says QO breakers are only UL tested and approved for QO, NQO, NQOD and NQ panelboards [Q3], that Homeline breakers are not classified for competitors' load centers [Q2], and that its load centers accept only Square D breakers [Q1].

Are Eaton BR breakers compatible with GE panels? Eaton: "BR breakers are UL approved to be used in the following loadcenters: Westinghouse, Challenger, Bryant, Cutler-Hammer, and Eaton BR loadcenters." [K6] For GE panels, Eaton's documented option is Type CL on its list [E1 p.4, p.8].

Sources

IDPublisherDocument / versionLinkKind
E0Eaton (hosted on Home Depot CDN)SA00304001E UL Classified Circuit Breaker Replacement Chart (PDF mod 2011-05-10), olderURL not recorded (Home Depot thdstatic CDN copy; obtained 2026-11-15 in research/directions/2026-11-15-new)primary-mirror
E1EatonIL00304001Y, visible imprint "Revised September 2024" (p.10); hidden text layers also contain "Revised May 2024" and REV. 24/27 markers; PDF mod 2025-06-05, 10 pplinkprimary
E3EatonBR003051EN (URL br003034en), July 2026, 4 pplinkprimary
K6Eaton Knowledge HubArticle 000006519 "Which loadcenters can BR breakers be installed in?", printed 2026-11-15 (no article date shown)linkprimary
Q1Schneider Electric / Square DFAQ FA109246, fetched 2026-11-15linkprimary
Q2Schneider Electric / Square DFAQ FA129931, fetched 2026-11-15linkprimary
Q3Schneider Electric / Square DFAQ FA124299, fetched 2026-11-15linkprimary
G1ABB Electrification USLCM announcement 2024-06-28, ABB document 1TQC114500E0003, 3 pplinkprimary
G2ABB (hosted on Home Depot CDN)PDF mod 2025-05-28, 2 pplinkprimary-mirror
G3ABB (hosted on Home Depot CDN)compatibility letter rev A 2025-05-22, 2 pplinkprimary-mirror
G4ABB Electrification USBuyLog Section 1 "Load centers, meter combos, and residential circuit breakers", document 9AKK108467A9432, "Section Updated 09/2026" (p.1-3), 72 pp; printed page 1-N = PDF page N; captured 2026-11-16linkprimary
G5ABB (Canada)"GE PowerMark Gold Load Centres CSA Selection Guide", 1SXP901001C0201, March 2020 (back cover), 16 pp; Canada / CSA; printed page n = PDF page n+2linkprimary
U1UL SolutionsMCCB Marking and Application Guide (web), fetched 2026-11-15linkprimary
C9U.S. CPSCnews release May 2007linkprimary
C13U.S. CPSCcpsc.gov recall web page, Recall Date November 19, 2004, recall number 05-515; printed to PDF in browser 2026-11-16, 4 pplinkprimary
O1U.S. OSHAElectrical Hazard Alert (undated in file)linkprimary

All documents fetched 2026-11-15 or 2026-11-16 and archived with SHA256 (see SOURCE-LIBRARY.csv). Kind: primary = issued by the manufacturer/agency; primary-mirror = manufacturer document hosted by a third party.

Related reference photographs
The interior of a breaker panel.
The interior of a breaker panel. This example does not identify your equipment.
Photo credit and licence

"EEUU(GE)BreakerpanelInnards.jpg" by The original uploader was Where at English Wikipedia., public domain (per Wikimedia Commons file page), via Wikimedia Commons: https://commons.wikimedia.org/wiki/File:EEUU(GE)BreakerpanelInnards.jpg Resized for the web.

Original Commons file and licence

Keep the reference with your question.

Retain the exact identifier, document revision, page and unresolved conditions. The lookup covers only one Eaton list; a result is not an equipment or installation assessment.