Square D: keep QO and Homeline separate.

Read Square D’s own statements beside the documents from classified breaker makers. Keep series, conditions and original pages separate.

Quick answer

  • Square D: "The Square D QO and Homeline load centers are UL tested, listed, and labeled to accept ONLY Square D circuit breakers." [Q1]
  • Square D, on its own breakers in other panels: QO breakers "are only UL tested and approved for use in QO, NQO, NQOD, and NQ panelboards" [Q3]. "The Homeline branch breakers are NOT classified to be used in competitors load centers." [Q2]
  • Eaton sells UL Classified Type CHQ for Square D QO loadcenters and Type CL for Square D HOMELINE loadcenters [E12 p.102, p.103].
  • Siemens describes Type QD as "UL Classified for use in place of Square D Type QO circuit breakers in Square D load centers" [S4 p.1].
  • ABB lists Type TQ as "3/4" UL Classified Circuit Breakers for use in *Square D **QO Load Centers." [G4 p.1-57]
  • Square D's warranty bulletin states: "Schneider Electric disclaims all liability for damage, injury or non-performance caused by the use or failure of incompatible or UL® classified circuit breakers." [Q4 p.1]
Residential breaker families: width and trip indication as the makers state them

Compare a printed dimension, not an installation permission. Equal width does not establish a listed or classified combination.

Eaton CH3/4 in. per poleE5 p.5
Eaton BR1 in. per poleE5 p.5
Eaton CL1 in. per poleE12 p.103
Eaton CHQ3/4 in. per poleE5 p.8
Square D QO3/4 in. per poleQ7 p.67
Square D Homeline1 in. per poleQ7 p.67
Siemens QP1 in. per poleS9 p.1
Siemens QD3/4 in. per poleS9 p.47
GE / ABB THQL1 in. per poleG1 p.1
GE / ABB THQP1/2 in. per poleG1 p.1
Original drawing and source annotations

The original drawing is schematic, not a product label, field measurement or installation instruction.

Open the original full-size SVG

"½" THQP"; ABB not accepting new orders as of October 2, 2024

Sources: E5 Eaton Residential Product Guide MZ00400002E p.5, p.8; K5 Eaton KB 000015509; E12 Eaton CA08100002E (2022) p.103; E1 Eaton IL00304001Y p.1; Q6 Square D 0730CT9801 p.3;

Q7 Square D 1100CT0501 pp.45, 67; S9 Siemens SPEEDFAX SF-17 pp.1, 47; S4 Siemens QD brochure p.1; G1 ABB THQP notice (June 28, 2024) p.1. The panel label governs.

Two fictional breaker-like housings each with a separate blank document folder.
AI-generated concept illustration. Keep each family’s source statement separate. These generic objects do not depict Siemens, GE, Eaton or Square D products or establish an interchangeability claim. Not technical evidence.

QO and Homeline: how Square D describes them

Square D's 2026 catalog compares the two load center lines in its Table 51 [Q7 p.67]:

Feature (Table 51 wording)QO load centersHomeline load centers
Circuit breaker format"3/4 in. per 1 Pole""1 in. per 1 Pole" [Q7 p.67]
Breakers"QO 3/4 in. breakers feature Visi-Trip trip to center position""Homeline 1 in. circuit breakers trip to center position" [Q7 p.67]
Bus bars"Tin-plated copper", "Shielded""Tin and copper plated aluminum", "Not shielded" [Q7 p.67]
40 space/circuit enclosure"33 3/4 in. Tall" (printed "Tail")"39 1/2 in. Tall" [Q7 p.67]
Plug-on neutral"PON circuit breakers installed on any space in select Load Centers""PON circuit breakers installed on any space" [Q7 p.67]
Warranty"Lifetime Limited"The Warranty row's Homeline cell prints "Combo cover (in carton) shipped with Load Center" [Q7 p.67]

The row label beside the breaker descriptions reads "UL Listed Only for Square D Circuit Breakers" [Q7 p.67]. The Homeline section repeats it: "UL Listed Only for Square D Breakers: 1-in. format breakers trip to center position." [Q7 p.45]

QO and QOB breakers

  • "QO (plug-on) and QOB (bolt-on) one-, two- and three-pole thermal-magnetic circuit breakers provide overcurrent protection and switching on ac and dc systems." [Q6 p.3]
  • Where each type is used [Q6 p.3]:
    • "Plug-on QO circuit breakers are for use in QO load centers, NQ and NQOD panelboards, OEM mounting bases, and Speed-D® switchboard distribution panels." [Q6 p.3]
    • "Bolt-on QOB circuit breakers are for use in NQO and NQOD panelboards." [Q6 p.3]
  • Standards: "QO and QOB circuit breakers are built to comply with UL Standard 489, CSA 22.2 No. 5, NOM/ANCE and NEMA Standard AB1". "QO circuit breakers are UL Listed under UL File E84967." [Q6 p.3]
  • Voltage ratings listed: "120 Vac", "208/120 Vac", "120/240 Vac", "240 Vac" and "48 Vdc (10–70 A for 1 and 2 pole circuit breakers, 10–60 A for 3 pole circuit breakers)" [Q6 p.4].
  • Trip indication: "When the circuit breaker has tripped, the handle assumes a center position and the red Visi-Trip indicator appears in a window in the circuit breaker case." [Q6 p.3]
Bus connection types named in the documents

Plug-on / bolt-on

Square D’s document names QO as plug-on and QOB as bolt-on. Q6 p.3

CTL / Non-CTL

The Eaton drawings distinguish a notched bus stab and rejection tab from an unnotched stab. The replacement conditions are in the document. E12 pp.78, 83

Simplified shapes for terminology only. No installation sequence or dimensional fit is shown.

Original drawing and source annotations

The original drawing is schematic, not a product label, field measurement or installation instruction.

Open the original full-size SVG

1968".

Sources: Q6 Square D 0730CT9801 (2008) p.3; Q3 Square D FAQ FA124299; E12 Eaton CA08100002E (Nov 2022) pp.78, 83; S9 Siemens SPEEDFAX SF-17 p.45. Schematic only; it does not show

how to install anything.

QO branch breakers by interrupting rating (Table 1)

AIRTypePoles and amperes
10,000QO1-pole 10–70 A; 2-pole 10–200 A; 3-pole 10–100 A [Q7 p.8]
10,000QOT (Tandems Non-CTL)1-pole 15–20 A [Q7 p.8]
10,000QO-EPD1-pole 15–30 A; 2-pole 15–60 A [Q7 p.8]
10,000QO-GFI1-pole 15–30 A; 2-pole 15–60 A [Q7 p.8]
10,000QO-AFI1-pole 15–20 A [Q7 p.8]
10,000QO-CAFI1-pole 15–20 A [Q7 p.8]
22,000QO-VH1-pole 15–30 A; 2-pole 15–200 A; 3-pole 15–100 A [Q7 p.8]
42,000QOH2-pole 40–125 A [Q7 p.8]
65,000QH1-, 2- and 3-pole 15–30 A [Q7 p.8]

Source: [Q7 p.8]. The table also lists QO-HID, QO-PL, QO-PLILC, QO-SWN, QO-VHGFI and QOB-VH [Q7 p.8].

Homeline branch breakers (Table 32, all 10,000 AIR)

TypePoles and amperes
HOM1-pole 15–50 A; 2-pole 15–125 A [Q7 p.47]
HOMT1-pole 15–30 A; 2-pole 15–50 A [Q7 p.47]
HOM-GFI1-pole 15–20 A; 2-pole 15–50 A [Q7 p.47]
HOM-AFI1-pole 15–20 A [Q7 p.47]
HOM-CAFI1-pole 15–20 A; 2-pole 15–20 A [Q7 p.47]
HOM-P1-pole 15–20 A [Q7 p.47]
HOM-BB2-pole 150–200 A [Q7 p.47]
HOM-DF, HOM-HM1-pole 15–20 A [Q7 p.47]
HOM-EPD1-pole 15–20 A; 2-pole 15–50 A [Q7 p.47]

Source: [Q7 p.47].

QOT: two descriptions in the same catalog

The 2026 catalog describes QOT tandems in two ways [Q7 pp.6–8]:

Catalog sectionWording
breaker catalog number guide"QO = Full size / QO Tandem Non-Class CTL"; "QOT = Tandem Class CTL" [Q7 p.6]
General Information"QOT (non-CTL)" [Q7 p.7]
Table 1"QOT (Tandems Non-CTL)" [Q7 p.8]

Square D's own statements on other makers' breakers

  • "The use of any other manufacturers' breakers, will VOID the UL listing and warranty of the product." [Q1]
  • "Square D disclaims all liability for damage, injury or non-performance caused by the use or failure of non-Square D circuit breakers." [Q1]
  • "NO. The Homeline branch breakers are NOT classified to be used in competitors load centers. Also, the use of the branch breakers in competitors load centers is NOT authorized by Square D." [Q2]
  • "No, the QO breakers are only UL tested and approved for use in QO, NQO, NQOD, and NQ panelboards." [Q3]
  • The residential warranty bulletin disclaims "all liability for damage, injury or non-performance caused by the use or failure of incompatible or UL® classified circuit breakers" [Q4 p.1].

Other makers' UL Classified breakers for Square D panels (shown beside Square D's statements)

DocumentStatement
Eaton catalog CA08100002E"Type CHQ Replacement Breakers for Square D Type QO Loadcenters"; "Type CHQ Classified Breakers 3/4-Inch (19.1 mm) per Pole"; "10 kAIC, 120 and 120/240 Vac" [E12 p.102]
Eaton catalog CA08100002EPage heading: "Type CL Replacement Breakers for Square D HOMELINE, General Electric, Crouse-Hinds, Thomas & Betts, Murray and ITE®/Siemens Loadcenters" [E12 p.103]
Eaton list IL00304001YSquare D meter center catalog numbers on p.2. Square D panelboard numbers under "CLCAF Specified (tested) Panelboard Catalog Numbers" on p.3. Square D panelboard numbers on p.10. Conditions on p.1 [E1 pp.1–3, 10]
Eaton list IL00304001Y, p.4 replacement tableSquare D standard HOM115–HOM150 / HOM215–HOM250 → CL115–CL150 / CL215–CL250; GF HOM115GFI–HOM120GFI → CL115GFT–CL130GFT; AF HOM115AFI–HOM120AFI → CL115AF–CL120AF; CAF HOM115CAFI–HOM120CAFI → CL115CAF–CL120CAF, CLCAF115–CLCAF120, CLAF115 and CLAF120; DF HOM115DF–HOM120DF → CLDF115–CLDF120 [E1 p.4]
Siemens Type QD brochure"Siemens Type QD circuit breakers are UL classified for use in specific Square D load centers in place of Square D QO circuit breakers (see listing on back)." "Siemens QD circuit breakers are available in 15 to 60 amps, single and double pole configurations and are rated at 120/240V AC." [S4 p.1]
Siemens Type QD brochureComparative guide: D115 ↔ QO115, D120 ↔ QO120 … D260 ↔ QO260 [S4 p.1]
ABB BuyLog Section 1 (updated 09/2026)"TQ CIRCUIT BREAKERS": "3/4" UL Classified Circuit Breakers for use in *Square D **QO Load Centers." "10 kAIC RMS symmetrical"; TQ1115–TQ1150 (1-pole), TQ2115–TQ2160 (2-pole) [G4 p.1-57]
Square D warranty bulletinDisclaims liability for "incompatible or UL® classified circuit breakers" [Q4 p.1]

Eaton's list sets these conditions: "EATON Type CL, CL GFCI & CL AFCI circuit breakers have been Classified by UL® for use in place of UL listed circuit breakers in UL listed panelboards/meter centers." "CAUTION: If the application requires breakers to be handle-tied, both Classified breakers must be the same manufacturer and type." The supply system is "Single-Phase, 3-Wire, 120/240 V~ Max. Available Short Circuit Current 10 kAIC". [E1 p.1]

Square D recalls and counterfeit notices

  • 2022: QO Plug-on-Neutral load centers "manufactured between February 2020 and January 2022, with date codes between 200561 and 220233" [C8].
  • 2004: QO and Homeline AFCI breakers "manufactured after March 1, 2004" with "a blue test button" and red date codes CN–JN [C7].
  • 2002: MA/MH breakers "manufactured between October 2000 and March 2002" [C12].
  • 1988: Series 1 two-pole GFCI breakers with "a yellow 'Push-To-Test' button" [C11].
  • 2006–2010: five distributor recalls of counterfeit "Square D" QO/QOB breakers [C5] [C6] [C14] [C15] [C16]. Genuine breakers have:
    • "the amp rating written on the handle in white paint on the front of the breaker" [C16];
    • "the Square D insignia molded onto the breaker side" [C16];
    • "a yellow chromate mounting clip with half of the top of the clip visible" [C16].
    • The same notice adds that "authentic Square D circuit breakers manufactured prior to 2003 did not have white paint on the amperage numbers" [C16].
What CPSC notices say genuine Square D QO breakers have

Original outline drawing (not a photo, not to scale). Feature wording is quoted from CPSC recall notices for counterfeit "Square D" breakers.

1 Amp rating on the handle

"the amp rating written on the handle in white paint

on the front of the breaker" (C5, C14, C15, C16).

C16 adds: "authentic Square D circuit breakers

manufactured prior to 2003 did not have white paint

on the amperage numbers".

2 Molded insignia

"the Square D insignia molded onto the breaker side"

(C5, C14, C15, C16).

3 Mounting clip

"a yellow chromate mounting clip with half of the

top of the clip visible" (C14, C15, C16; C5 says

"yellow chromate clip").

4 Arc chute opening (one notice)

"on the side of the breaker, where wire terminal

screw is located, the arc shoot opening should have

squared corners with the bottom edge of the opening

angled up" (C6).

CPSC: "If your breaker does not match this description, it could be counterfeit." (C5) CPSC tip: "Look for a certification mark from an independent testing

organization, such as Underwriters Laboratories (UL), and the manufacturer's label." (C9)

These historical notice descriptions are not a standalone authenticity test. Keep the applicable notice and its product/date scope. C16

Original drawing and source annotations

The original drawing is schematic, not a product label, field measurement or installation instruction.

Open the original full-size SVG

Sources: CPSC recall notices C5 (Miami Breaker, Aug 2, 2010), C6 (Scott Electric, Nov 16, 2006), C14 (Connecticut Electric, Oct 30, 2007), C15 (North American Breaker

Co., Dec 27, 2007), C16 (Specialty Lamp International, May 27, 2008); C9 CPSC counterfeit warning (May 2007). C16 remedy: "Consumers should contact Specialty to

determine if the breaker they have is counterfeit".

What to bring to an electrician

  • The load center catalog number and date code from inside the door [C8] [Q7 p.33].
  • The breaker list on the wiring diagram: "Square D circuit breakers that may be used in this load center" [Q7 p.34, p.60].
  • If a classified breaker is proposed: the matching IL00304001Y page and its conditions [E1 p.1] or the QD listing [S4 p.2], together with Square D's statements above [Q1] [Q4 p.1].

Sources

IDPublisherDocument / versionLinkKind
E1EatonIL00304001Y, visible imprint "Revised September 2024" (p.10); hidden text layers also contain "Revised May 2024" and REV. 24/27 markers; PDF mod 2025-06-05, 10 pplinkprimary
E12EatonCA08100002E Volume 1 Residential and Light Commercial, November 2022, full 105 pp (PDF created 2022-11-02); captured 2026-11-15linkprimary
S4Siemens (cache.industry.siemens.com)SIE_BR_QD (PDF mod 1999-06-05), 2 pplinkprimary
Q1Schneider Electric / Square DFAQ FA109246, fetched 2026-11-15linkprimary
Q2Schneider Electric / Square DFAQ FA129931, fetched 2026-11-15linkprimary
Q3Schneider Electric / Square DFAQ FA124299, fetched 2026-11-15linkprimary
Q4Schneider Electric / Square DData bulletin 0700DB2001 (PDF mod 2020-07-24), 2 pplinkprimary
Q6Schneider Electric / Square DCatalog 0730CT9801R1/08 "QO and QOB Miniature Circuit Breakers", Class 730, 07/2008, 40 pp (download.schneider-electric.com), captured 2026-11-15linkprimary
Q7Schneider Electric / Square DCatalog 1100CT0501 "Square D QO and Homeline Load Centers and Enclosures", 06/2026 (footer Rev.03), 88 pp; printed page = PDF page; captured 2026-11-15linkprimary
G4ABB Electrification USBuyLog Section 1 "Load centers, meter combos, and residential circuit breakers", document 9AKK108467A9432, "Section Updated 09/2026" (p.1-3), 72 pp; printed page 1-N = PDF page N; captured 2026-11-16linkprimary
C5U.S. CPSCrecall 2010-08-02linkprimary
C6U.S. CPSCrecall 2006-11-16linkprimary
C7U.S. CPSCrecall 2004-11-03linkprimary
C8U.S. CPSCrecall 2022-06-16linkprimary
C11U.S. CPSCcpsc.gov recall web page, Recall Date April 13, 1988, recall number 88-022; Units "Approximately 80,000"; printed to PDF in browser 2026-11-16, 4 pplinkprimary
C12U.S. CPSCcpsc.gov recall web page, Recall Date August 09, 2002, recall number 02-556; printed to PDF in browser 2026-11-16, 4 pplinkprimary
C14U.S. CPSCcpsc.gov recall web page, Recall Date October 30, 2007, recall number 08-054; printed to PDF in browser 2026-11-16, 4 pplinkprimary
C15U.S. CPSCcpsc.gov recall web page, Recall Date December 27, 2007, recall number 08-151; printed to PDF in browser 2026-11-16, 4 pplinkprimary
C16U.S. CPSCcpsc.gov recall web page, Recall Date May 27, 2008, Release #08-286; printed to PDF in browser 2026-11-16, 5 pplinkprimary

All documents fetched 2026-11-15 or 2026-11-16 and archived with SHA256 (see SOURCE-LIBRARY.csv). Kind: primary = issued by the manufacturer/agency; primary-mirror = manufacturer document hosted by a third party; primary (vendor) = issued by the maker of the replacement product described.

Related reference photographs
Front and back view of a circuit breaker.
Front and back view of a circuit breaker. This example does not identify your equipment.
Photo credit and licence

"Schneider Electric Double Single-Pole 15-Amp Circuit Breaker - Front and Back View.JPG" by Kevin Kiefuik, licensed CC BY-SA 3.0 (https://creativecommons.org/licenses/by-sa/3.0), via Wikimedia Commons: https://commons.wikimedia.org/wiki/File:Schneider_Electric_Double_Single-Pole_15-Amp_Circuit_Breaker_-_Front_and_Back_View.JPG Resized for the web.

Original Commons file and licence

Keep the reference with your question.

Retain the exact identifier, document revision, page and unresolved conditions. The lookup covers only one Eaton list; a result is not an equipment or installation assessment.

Search Eaton’s document Record a source discrepancy